Mebay Bus Tie Mains Generator Auto Synchronizer Synchronization Panels DC110D
DC110 series parallel controllers are suitable for manual/automatic parallel systems of multiple generator sets with single or multiple mains power, enabling automatic start-up and shutdown, parallel operation, data measurement and alarm protection of multiple generator sets.
The parallel controller has a wide choice of modes for parallel operation with the mains, such as genset fixed active power, reactive power/power factor output, mains peak lopping and uninterruptedly restore to mains supply.
Main Features* 4.3inch TFT colorful big screen LCD, Available in 9 languages, users language set if necessary.
* The standard ETHERNET communication interface can be connected to the GSCLOUD generator cloud control platform, and the status of the generator set can be monitored remotely through the WEB platform and mobile APP; the ETHERNET interface supports the Modbus-RTU protocol, and the controller parameters can be set through the PC;
* MSC CAN communication interface, capable of communicating with multiple generator sets* For mains, controller has over voltage, under voltage, over frequency, under frequency ,loss of phase and phase sequence wrongdetection functions; For bus, controller has over current, over power, loss of phase, phase sequence wrong detection functions. *Synchronization parameters: Voltage Difference Between Bus and Mains, Frequency Difference Between Bus and Mains, PhaseDifference Between Bus and mains, multiple running modes in auto state: AMF (Automatic Mains Failure), Island Mode, Fixed Power,Peak Lopping Mode and Load Takeover Mode.
*Ramp on and ramp off function.
| Options | Parameters |
| Working voltage | DC8V—-36V Continuous |
| Power consumption | Standby24VMAX2W |
| Working24VMAX5W | |
| AC Voltage Input | 1P2W 30VAC-360VAC (ph-N) |
| 2P3W 30VAC-360VAC (ph-N) | |
| 3P3W 60VAC-620VAC (ph-N) | |
| 3P4W 30VAC-360VAC (ph-N) | |
| Alternator Frequency | 50HZ/60HZ |
| AUX. OUTPUT 1-3 | Max 5Amp DC+VE Supply voltage |
| AUX. OUTPUT 4 | 250V/5 AMP Non-contact normally Open/Closed output |
| AUX. OUTPUT 5 | 250V/16 AMP Non-contact normally Open/Closed output |
| AUX. OUTPUT 6 | 250V/16 AMP Non-contact normally Closed output |
| AUX. OUTPUT 7-8 | Max 16Amp DC+VE Supply voltage |
| AUX. Input | Available if connecting with Battery – |
| USB | Type-A Type-B |
| RS485 | Isolated Modbus-RTU protocol |
| ENTHERNET | RJ45 10/100Mbps adaptive network interface;Cloud Protocol and TCP/IP Modbus Protocol; |
| Working condition | DC110D: -25-65DC110MR: -40C ~+70 CDisplay Heater: -10C turn on; -5C turn off |
| Storage condition | -40-85 |
| Protection Level | IP65when waterproof rubber gasket is added between controller and its panel |
| Overall dimension | 241mm*177mm*45mm |
| Panel cutout | 220mm*160mm |
| Weight | 1Kg |